I believe you will not be unfamiliar with the rolling shutter door. At present, you can often see the shadow of the rolling shutter door, whether it is a private garage or the front door. After installing the rolling shutter door, it will ensure the internal safety and greatly improve the overall safety performance. What are the installation requirements and application scope of Jinan rolling shutter door? Now, with this article, let's learn more about it.
卷帘门的设置要求:
Setting requirements of rolling shutter door:
1、替代传统门的卷帘门应满足防火墙耐火性的判定条件,或两侧设置冷却水帘。计算水量时,应考虑火灾持续时间不小于3小时
1. The rolling shutter door instead of the traditional door shall meet the judgment conditions of the fire resistance of the firewall, or the cooling water curtain shall be set on both sides. When calculating the water volume, the fire duration shall not be less than 3 hours
济南卷帘门
2、位于疏散走道和前室内的卷帘门应具有延时下降功能。卷帘两侧应设置开关装置,开关装置应采用电动和手动控制。
2. The rolling shutter door located in the evacuation walkway and front room shall have the function of delayed descent. Both sides of the roller shutter shall be equipped with switching devices, which shall be electrically and manually controlled.
3、发生火灾时需要自动下降的卷帘门应具有信号反馈功能。
3. The rolling shutter door that needs to be lowered automatically in case of fire shall have signal feedback function.
4、应有防火和防烟密封措施。当两侧压差为20Pa时,烟气泄漏小于0.2m/min。
4. Fire and smoke proof sealing measures shall be taken. When the pressure difference between two sides is 20Pa, the flue gas leakage is less than 0.2m/min.
5、不宜使用侧卷帘门。
5. Side rolling shutter doors should not be used.
6、卷帘门的耐火性不得低于规范规定的部件耐火要求。
6. The fire resistance of rolling shutter door shall not be lower than the fire resistance requirements of components specified in the specification.
卷帘门的应用范围:
Application scope of rolling shutter door:
一般设置在电梯厅和自动扶梯周围、中庭与楼层走道和大厅相通的开口处、生产车间的大面积工艺开口处以及难以设置防火墙的地方。
It is generally set around the elevator hall and escalator, the opening between the atrium and the floor walkway and hall, the large-area process opening of the production workshop and the place where it is difficult to set a firewall.
需要注意的是,为了保证安 全,除中庭外,当防火分隔部分的宽度不大于30m时,卷帘门的宽度不应大于10m。当防火分隔部分宽度大于30m时,卷帘门宽度不应大于防火分隔部分宽度的1/3,不应大于20m。
It should be noted that in order to ensure safety, except for the middle court, when the width of the fire separation part is not greater than 30m, the width of the rolling shutter door shall not be greater than 10m. When the width of the fire separation part is greater than 30m, the width of the rolling shutter door shall not be greater than 1 / 3 of the width of the fire separation part, and shall not be greater than 20m.
济南卷帘门的设置要求以及应用范围是什么?上文就是分享给大家的答案了,希望大家在看完上文之后,会对此有更深入的了解,随着近几年卷帘门的普及,大家在寻找厂家安装的时候,要找一家靠谱的厂家进行安装,这样能保证卷帘门的质量,以及日后所需求的售后服务。
What are the setting requirements and application scope of Jinan roller shutter door? The above is the answer shared to you. I hope you will have a deeper understanding of this after reading the above. With the popularity of roller shutter doors in recent years, when looking for manufacturers to install, you should find a reliable manufacturer to install them, so as to ensure the quality of roller shutter doors and the after-sales service required in the future.